Superheat and subcooling: what four readings can and can’t tell you
A simplified split cooling system with a fixed-orifice metering device. Pick a condition, read the gauges and line clamps, then watch the two calculated numbers appear from what the refrigerant is doing inside the coils.
1Pick a condition to simulate
▾Tap a condition. Tap the lettered tags A–D on the machine to see each reading.
2Inspect the four readings
3Calculate
Saturation temperature is the boiling/condensing point for the gauge pressure. Every number here uses one unit system, and differences are in temperature-difference units.
Why these readings alone are not a diagnosis
- Targets move. A fixed-orifice system’s expected superheat changes with indoor and outdoor conditions; the equipment maker’s data sets the target, not a single number.
- Different faults overlap. Low superheat can come from overcharge or from poor airflow; high superheat from a low charge or from a restriction. Subcooling and airflow help separate them, and still don’t settle it.
- Measurements can mislead. Sensor contact, insulation, gauge accuracy, running time and where the lines are read all change the answer.
How the model works
Each condition is a set of example saturation and line temperatures. Superheat and subcooling are computed from the four readings exactly as shown above. Evaporator and condenser colours show how much of each coil carries superheated vapor or subcooled liquid. Airflow, flow speed, filter and gauges follow the same state.
SH = A − B SC = D − C